Specification

Application:

Fastening of all types of single- and multi-conductor high and low voltage cables (1kV to 765 kV)
Especially suitable for fastening in single and trefoil formation of single-conductor cab

Material:

Polyamide, fiberglass-reinforced, coloured black,
flame resistant , special protection against ultraviolet rays,
free of halogenes, fully recycable

Properties:

Resistance to: ultraviolet rays, ozone, oils, fuels, alkalis, radioactive rays
Flame resistance: UL94 V-0
classification following DIN 5510, part 2, flamability class S3
Thermal expansion: 0,01 % pro 10°C temperature increase
Tensile strength: 120 N/mm²
Flexural strength: 210 N/mm²

Temperature range:

Ambient temperatures: up to - 60 °C
Continuous operation: up to 120 °C
Short heating: up to 220 °C admissible
Operation life: more than 37 years of maintenance- and failure-free operation

legal compliance:

Directive 2002/95/EC (RoHS)
Regulation (EC) No. 1907/2006 (REACH)

Constructional Features:

  • Particularly high mechanical strength and heat resistance due to fibreglass-reinforced polyamide
  • Safe restraint of dynamic forces of high short-circuit currents
  • Test reports from neutral laboratories regarding dynamic short-circuit currents, up to 180 kA, and the fire-resistance of the Cable Clamps
  • Low mechanical pressure on the cables due to very wide clamping length
  • Unrestricted application both indoor and outdoor in extreme climates such as deserts, tropics, high mountains, arctic climate, coastal salt fogs, flooding, ozone, due to special resistance to ageing, ozone and ultraviolet rays
  • Secure fixation without damage to the cables at high short-circuit currents
  • Easy to mount without special instruments and maintenance-free
  • Fastening of Cable Clamps adaptable to all local conditions
  • Operation in all voltage ranges, 1 kV to 765 kV
  • For single, trefoil, quad and bundled short-circuit proof cable applications
  • Highest short-circuit strength
  • High flame-resistance according to UL94 V-0 and DIN 5510 Part 2 flammability class S3
  • Chemical resistance to oils, fuels, alkalis, radioactive rays
  • Absolute resistance to ultraviolet rays due to special additive
  • Lifetime experience: more than 37 years of maintenance- and failure-free operation
  • Ambient temperatures down to below -60 °C
  • Continuous operation up to 120 °C
  • Permitted short-term heating up to 220 °C
  • Minimization of contact pressure to avoid damage of cables during short-circuit fault
  • Unrestricted operation indoor and outdoor in extreme climates: deserts, tropics, high mountains, polar climate, coastal salt fogs, flooding, ozone resistance
  • Cyclic stress due to alternation of load
  • Easy and rapid installation without special tools, also subsequently after the installation of cables
  • Fastening adaptable to local conditions
  • Non-toxic, non-hazardous, halogen-free, non-metallic, non-magnetic and corrosion-free material
  • Complies with Directive 2002/95/EC (RoHS) and Regulation (EC) No. 1907/2006 (REACH)
  • Reusable after rebuilding or temporary usage
  • Compact design, thus easy to handle
  • Worldwide application in more than 120 countries