Series KS

Data

Application:

Fastening of single-conductor cables in trefoil formation

unrestricted application indoors and outdoors

For cables with outer diameters of:22 mm to 46 mm
Mechanical resistance to short-circuits:13 000 N
Max. torque for tightening screws:5 Nm

Outline

Dimensions

Dimensions in mm

Type DØ DØ* L B l dØ H1 H2 h a
KS 25/36 25-36 22-33 150 80 110 12 55-75 77-97 35 19
KS 33/46 33-46 30-43 170 80 130 12 55-85 85-115 35 15

DØ: outer cable diameter     DØ*: ~ with Elastic Inlays

Application with Elastic Inlay

  • as secure fixation of the cables and absorption of forces due to the weight of the cables at vertical sections in any height (wind turbine generators, masts, shafts)
  • as extension of the clamping range for the fixation of cables with smaller outer diameters


Fastening Example