Series KH

Data

Application:

Fastening of single-conductor cables in trefoil formation for high short circuit forces

unrestricted application indoors and outdoors

For cables with outer diameters of:59 mm to 165 mm
Mechanical resistance to short-circuits:30 000 N
Max. torque for tightening screws:8 Nm

Outline

Dimensions

Dimensions in mm

Type DØ DØ* L B l dØ H1 H2 h a
KH 62/75 62-75 59-72 225 90 185 18 114-142 172-200 80 30
KH 73/86 73-86 70-83 250 100 210 18 119-147 192-220 85 30
KH 84/97 84-97 81-94 270 100 230 18 128-156 214-242 95 30
KH 95/107 95-107 92-104 290 100 250 18 136-164 244-262 103 30
KH 105/117 105-117 103-114 310 100 270 18 144-178 248-282 108 30
KH 115/140 115-140 112-137 365 120 320 18 182-242 270-330 145 35
KH 138/165 138-165 135-162 500 140 420 20 215-310 295-390 165 40

DØ: outer cable diameter     DØ*: ~ with Elastic Inlays

Application with Elastic InlayElastic Inlay

  • as padding of the cables (for diameters ≥ 60 mm) to avoid damage of the cables under strain and/or change of surrounding temperature
  • as secure fixation of the cables and absorption of forces due to the weight of the cables at vertical sections in any height (wind turbine generators, masts, shafts)

 

Additionally, the Distance Wedge is needed cables with impregnated paper insulation for high- and extra high-voltage. For the range of outer cable diameter check Distance Wedge data sheet.