Technical Details

Application

  • Short circuit resistant fastening of all types of single and multi-core cables from extra high to low voltage
  • Single, trefoil, parallel, bundled or stacked fastening of energy cables

Material

High-grade polyamide, fibreglass-reinforced, coloured black, with special UV protection, fully recyclable, LSZH (low smoke, zero halogen), silicone free, self-extinguishing, zero-halogen (free of fluorine, chlorine, bromine, iodine), non-toxic, non-corrosive, non-metallic, non-magnetic

Temperature range

Ambient temperatures
down to -60°C*

Continuous operation
up to 120°C

Permitted short-term heating
up to 220°C

Operation life
more than 45 years of maintenance-
and failure-free operation

Legislation

Legal compliance

  • Regulation (EG) Nr. 1907/2006 (REACH regulation)
  • Directive 2015/863/EU (RoSH)
  • SJ/T 11363-2006 (China RoSH)
  • United Arab Emirates Restrictions No. 10 (UAE RoSH)

IEC 61914 STANDARD

îd-Technik Cable Clamps have been type-tested by accredited test institutes to the international standard IEC 61914.

Properties

Resistance to
Ultraviolet rays, ozone, mineral oils, fuels, salts, alkalis, alcohol, hydrocarbons, ketones, ether, termites and radioactive rays*

Flame resistance
UL 94 5 VA (IEC 60695-11-20)
500 Watt flame test method

UL 94 V-0 (IEC 60695-11-10)
50 Watt flame test method

IEC 61914 following IEC 60695-11-5
Needle-flame test method

Classification following DIN 5510,
part 2: flammability class S3

Thermal expansion
0,01 % per 10°C temperature increase

Tensile strength
120 N/mm2

Flexural strength
210 N/mm2

Resistance to impact
Very heavy, type-tested to IEC 61914, at -60°C

Lateral load test
Type-tested to IEC 61914, in x- and
y-direction, at 120°C

Axial load test (N)
Type-tested to IEC 61914, at 120°C

Dynamic resistance to short circuits
Type-tested to IEC 61914, suitable to withstand multiple short circuits

Constructional features

  • Particularly high dynamic and mechanical strength and heat resistance due to special fibreglass-reinforced polyamide
  • Safe restraint of dynamic forces of high short circuit currents, without damage to the cables, also for multiple short circuits
  • Type-tested to IEC 61914 – cable cleats for electrical installations - reports from accredited institutes regarding dynamic short circuit currents, the fire-resistance of the material, and mechanical properties of the Cable Clamps are available
  • Very low surface pressure on cables due to Cable Clamps’ large contact area
  • Unrestricted application both indoor and outdoor in extreme climates such as deserts, tropics, high altitudes, arctic climate, coastal salt fogs, flooding, ozone due to special resistance to ageing, ultraviolet rays and ozone
  • Easy to mount without special instruments and maintenance-free
  • Fastening of Cable Clamps adaptable to all local conditions