Test:
Three 10-KV single-core cables with cross-linked polyethylene insulation and
cross sections of 400 mm² (0.62 sq.in) were laid out in parallel and fastened
to a frame using the cable clamps in question.
| Test No. |
Is kA |
a cm |
l m |
F N |
| 189-79/73 |
65,3 |
11,5 |
0,9 |
5.900 |
| 189-79/74 |
80,2 |
11,5 |
0,9 |
8.950 |
| (189-79/80 |
112 |
11,5 |
0,9 |
17.400) |
Findings:
Cable Clamps withstood forces of 5.900 N and 8.950 N without any damage.
However, considerable bending of cables was observed.
Photographs 1 ( Image)
and 2 ( Image) show test set-up before and after testing.
|